 Convert To Display Actual Units
 Convert to display of actual units measured. Eg. 12 mA or 3 V input can be set to display 250 gallons (946 liters).
Transmitter outputs are typically set for 4 to 20 mA with 4mA representing the low end of the range and 20 mA representing the high end of the range. For example in an application measuring the volume in a tank, a level transducer transmits 4mA when the tank is empty and transmits 20 mA when the tank is at full capacity of 500 gallons.

This type of transmitter has several benefits in industrial applications such as this one. The “live zero” of 4 mA indicates the system and “loop’ is functioning. If the signal falls below 4 mA it indicates an open loop or other failure. A current signal is much more immune to electrical noise than a voltage signal, since only a parasitic or leakage current can cause an error. A current signal can be transmitted over longer distances than a voltage as long as the loop supply voltage can handle the voltage drop due to lead resistance.

The DPL-3 Series panel meters can be easily adjusted to read 000 with a 4 mA input and 500 with a 20mA input. Other intermediate inputs such as 8 mA would display a reading of 125 gallons, and 14 mA would display 313 gallons.

If a hose-proof & splash-proof display with larger digits is desired, the DPL-807 can be substituted for the DPL-3. All these LCD meters are powered directly from the 4 to 20 mA signal eliminating the need for additional power supplies and simplifying the connection without requiring supply isolation. If backlighting is desired it can be powered directly from the loop supply and is isolated from the meter.

If the volume is to be displayed in other units, such as liters, the meters can be simply readjusted to display the level in liters. In this example 500 gallons is equivalent to 1893 liters, so the meter would be readjusted to display 1893 with a 20 mA input.

In the event that the converted value was greater than 2000, e.g. 1800 gallons is 6814 liters, a 4 ˝ digit 20,000 count meter, the DPL-4, could be substituted for the DPL-3, and adjusted for the higher readings.
Related products:
 

DPV-3 Series - Voltage Powered, 3 1/2 digit LCD Digital Panel Meters Adjustable Voltage Input  

DPV-4 Series - Voltage Powered, 4 1/2 digit LCD Digital Panel Meters Adjustable Voltage Input  

DPV-809 Series - LARGE LCD Rangeable Voltage Digital Panel Meters - 3 1/2 digit  

Other Voltage/Loop Meters
 
 
   
  Click here to ask us a question NEW: Download a PDF of All Panel Meters:
  All Panel Meters PDF
(compressed zip file, 4.1 MB;)

 
This PDF does not include sensors or switches


 


Distributors welcome.
Panel Meters | Count / Time Meters | Sensors
HVAC Controls | Switches | View All Categories
Home | PDF Center |
Contact Us
Acculex / HR Components
PO Box 10300 - Bedford NH 03110
888-472-6676 phone - 888-210-0119 fax  
 (International:  1-603-472-4727 phone -  1-603-472-2159 fax)